← Main psychrometric calculator
Enthalpy and Vapour Pressure to Dry Bulb Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate dry bulb temperature.
Calculator inputs
Dry Bulb Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = 0.622 × Pv / (P − Pv)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
Reading dry bulb temperature
Air temperature measured by a dry, shielded thermometer.
The input calculation above gives the dry bulb temperature directly or by solving for it.
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Vapour Pressure 1.6191793 kPa · height 0 m
Dry Bulb Temperature = 27.00 °C
More calculations with these inputs
Enthalpy and Vapour Pressure to All Properties
- Enthalpy and Vapour Pressure to Specific Humidity Converter
- Enthalpy and Vapour Pressure to Relative Humidity Converter
- Enthalpy and Vapour Pressure to Wet Bulb Temperature Converter
- Enthalpy and Vapour Pressure to Specific Volume Converter
- Enthalpy and Vapour Pressure to Dew Point Temperature Converter