Psychrometric quantities and formulas
Definitions, units, and the moist-air model used by the calculators.
Quantity definitions
| Quantity | Report notation | SI unit | Definition |
|---|---|---|---|
| Dry Bulb Temperature | DB | °C | Air temperature measured by a dry, shielded thermometer. |
| Specific Humidity | SH | kg water/kg moist air | Mass of water vapour divided by the total mass of moist air. |
| Relative Humidity | RH | % | Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature. |
| Enthalpy | ET | kJ/kg dry air | Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state. |
| Wet Bulb Temperature | WB | °C | The temperature approached when water evaporates into air adiabatically until the air reaches saturation. |
| Specific Volume | SV | m³/kg dry air | Volume occupied by the moist-air mixture per kilogram of dry air. |
| Vapour Pressure | PV | kPa | The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure. |
| Dew Point Temperature | DP | °C | The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice. |
| Total Pressure | PT | kPa | The combined pressure of dry air and water vapour. |
| Height Above Sea Level | z | m | Elevation in metres measured relative to mean sea level. |
Model and calculation range
The desktop Psychrometric Tools project used a standard-atmosphere pressure approximation and moist-air relationships for an Atmospheric Water Generator (AWG). The web calculator uses the project's pressure, enthalpy and volume constants, continuous saturation-pressure equations, and a wet bulb energy balance.
Enter dry bulb temperatures from −60 to 160 °C, wet bulb and dew point temperatures from −100 to 160 °C, and altitudes from −500 to 11,000 m, or supply a positive total pressure directly. Valid moist-air states have vapour pressure below total pressure and at or below saturation. Very dry air can have a dew point below the calculation range.
Moist-air formulas
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
For overlap near freezing, the wet bulb calculation uses the liquid branch when available.
References
- Psychrometric Tools project report and Python GUI
- American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), Handbook: Fundamentals, Chapter 1, Psychrometrics. See also the PsychroLib formula reference.