Psychrometric quantities and formulas

Definitions, units, and the moist-air model used by the calculators.

Quantity definitions

QuantityReport notationSI unitDefinition
Dry Bulb TemperatureDB°CAir temperature measured by a dry, shielded thermometer.
Specific HumiditySHkg water/kg moist airMass of water vapour divided by the total mass of moist air.
Relative HumidityRH%Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
EnthalpyETkJ/kg dry airSensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
Wet Bulb TemperatureWB°CThe temperature approached when water evaporates into air adiabatically until the air reaches saturation.
Specific VolumeSVm³/kg dry airVolume occupied by the moist-air mixture per kilogram of dry air.
Vapour PressurePVkPaThe portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.
Dew Point TemperatureDP°CThe temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.
Total PressurePTkPaThe combined pressure of dry air and water vapour.
Height Above Sea LevelzmElevation in metres measured relative to mean sea level.

Model and calculation range

The desktop Psychrometric Tools project used a standard-atmosphere pressure approximation and moist-air relationships for an Atmospheric Water Generator (AWG). The web calculator uses the project's pressure, enthalpy and volume constants, continuous saturation-pressure equations, and a wet bulb energy balance.

Enter dry bulb temperatures from −60 to 160 °C, wet bulb and dew point temperatures from −100 to 160 °C, and altitudes from −500 to 11,000 m, or supply a positive total pressure directly. Valid moist-air states have vapour pressure below total pressure and at or below saturation. Very dry air can have a dew point below the calculation range.

Moist-air formulas

q = W / (1 + W)
W = 0.622 × Pv / (P − Pv)
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
RH = 100 × Pv / Psat(Tdb)
Pv = P W / (0.622 + W)
Psat(Tdp) = Pv
h(Tdb, W) + (Ws(Twb) − W) hf(Twb) = h(Twb, Ws(Twb))
W = q / (1 − q)
hf(Twb) = 4.186 Twb for Twb ≥ 0 °C
hf(Twb) = −333.6 + 2.1 Twb for Twb < 0 °C
Ws(Twb) = 0.622 Psat(Twb) / [P − Psat(Twb)]

Symbols

Tdb
Dry bulb temperature (DB), in °C.
Twb
Wet bulb temperature (WB), in °C.
Tdp
Dew point temperature (DP), in °C.
q
Specific humidity (SH), in kg water/kg moist air.
W
Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
Ws
Saturated value of W at the indicated temperature.
RH
Relative humidity, in percent.
h
Moist-air enthalpy (ET), in kJ/kg dry air.
hf
Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
v
Specific volume (SV), in m³/kg dry air.
Pv
Water vapour partial pressure (PV), in kPa.
Psat
Saturation vapour pressure at the temperature in parentheses, in kPa.
P
Total atmospheric pressure (PT), in kPa.

For overlap near freezing, the wet bulb calculation uses the liquid branch when available.

References