Relative Humidity and Dew Point Temperature to Enthalpy Converter
Enter the known properties and either total pressure or height above sea level to calculate enthalpy.
Calculator inputs
Enthalpy
kJ/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Psat(Tdb) = 100 Pv / RH
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Relative Humidity 45.389339 % · Dew Point Temperature 14.196543 °C · height 0 m
Enthalpy = 52.90 kJ/kg dry air
More calculations with these inputs
Relative Humidity and Dew Point Temperature to All Properties
- Relative Humidity and Dew Point Temperature to Dry Bulb Temperature Converter
- Relative Humidity and Dew Point Temperature to Specific Humidity Converter
- Relative Humidity and Dew Point Temperature to Wet Bulb Temperature Converter
- Relative Humidity and Dew Point Temperature to Specific Volume Converter
- Relative Humidity and Dew Point Temperature to Vapour Pressure Converter