Relative Humidity and Specific Volume to Enthalpy Converter
Enter the known properties and either total pressure or height above sea level to calculate enthalpy.
Calculator inputs
Enthalpy
kJ/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Find the dry bulb temperature by matching the supplied enthalpy or specific volume along the constant relative humidity curve.
Pv = (RH / 100) × Psat(Tdb)
W = 0.622 × Pv / (P − Pv)
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Relative Humidity 45.389339 % · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Enthalpy = 52.90 kJ/kg dry air
More calculations with these inputs
Relative Humidity and Specific Volume to All Properties
- Relative Humidity and Specific Volume to Dry Bulb Temperature Converter
- Relative Humidity and Specific Volume to Specific Humidity Converter
- Relative Humidity and Specific Volume to Wet Bulb Temperature Converter
- Relative Humidity and Specific Volume to Vapour Pressure Converter
- Relative Humidity and Specific Volume to Dew Point Temperature Converter