← Main psychrometric calculator
Specific Humidity and Dew Point Temperature Consistency Check
Compare two moisture readings at the selected total pressure or altitude.
Calculator inputs
Expected Dew Point Temperature
°C
Calculation history
No calculations saved on this page yet.
Why this pair is dependent
At a given total pressure, these readings describe the same moisture content. The calculator gives the expected second reading for comparison. An independent reading such as dry bulb temperature is needed to determine a complete moist-air state.
W = q / (1 − q)
Pv = P W / (0.622 + W)
Psat(Tdp) = Pv
Symbols
- Tdp
- Dew point temperature (DP), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Direct converters
- Specific Humidity to Dew Point Temperature Converter
- Dew Point Temperature to Specific Humidity Converter
Use an independent input
Worked example
Specific Humidity 0.01 kg water/kg moist air · Dew Point Temperature 14.196543 °C · height 0 m
Expected Dew Point Temperature = 14.20 °C