Specific Humidity and Specific Volume to Enthalpy Converter
Enter the known properties and either total pressure or height above sea level to calculate enthalpy.
Calculator inputs
Enthalpy
kJ/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Tdb = P × v / [0.2871 (1 + W/0.622)] − 273.15
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- v
- Specific volume (SV), in m³/kg dry air.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Enthalpy = 52.90 kJ/kg dry air