Specific Humidity and Vapour Pressure Consistency Check
Compare two moisture readings at the selected total pressure or altitude.
Calculator inputs
Expected Vapour Pressure
kPa
Calculation history
No calculations saved on this page yet.
Why this pair is dependent
At a given total pressure, these readings describe the same moisture content. The calculator gives the expected second reading for comparison. An independent reading such as dry bulb temperature is needed to determine a complete moist-air state.
W = q / (1 − q)
Pv = P W / (0.622 + W)
Symbols
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Direct converters
Use an independent input
Worked example
Specific Humidity 0.01 kg water/kg moist air · Vapour Pressure 1.6191793 kPa · height 0 m
Expected Vapour Pressure = 1.61918 kPa