← Main psychrometric calculator

Specific Volume and Vapour Pressure to Specific Humidity Converter

Enter the known properties and either total pressure or height above sea level to calculate specific humidity.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Specific Humidity

— kg water/kg moist air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.

    W = 0.622 × Pv / (P − Pv)
    Tdb = P × v / [0.2871 (1 + W/0.622)] − 273.15

    Formula for specific humidity

    Mass of water vapour divided by the total mass of moist air.

    q = W / (1 + W)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    q
    Specific humidity (SH), in kg water/kg moist air.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    v
    Specific volume (SV), in m³/kg dry air.
    Pv
    Water vapour partial pressure (PV), in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Specific Volume 0.86427316 m³/kg dry air · Vapour Pressure 1.6191793 kPa · height 0 m

    Specific Humidity = 0.0100000 kg water/kg moist air