← Main psychrometric calculator
Specific Volume and Vapour Pressure to Specific Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate specific humidity.
Calculator inputs
Specific Humidity
kg water/kg moist air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = 0.622 × Pv / (P − Pv)
Tdb = P × v / [0.2871 (1 + W/0.622)] − 273.15
Formula for specific humidity
Mass of water vapour divided by the total mass of moist air.
q = W / (1 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Specific Volume 0.86427316 m³/kg dry air · Vapour Pressure 1.6191793 kPa · height 0 m
Specific Humidity = 0.0100000 kg water/kg moist air
More calculations with these inputs
Specific Volume and Vapour Pressure to All Properties
- Specific Volume and Vapour Pressure to Dry Bulb Temperature Converter
- Specific Volume and Vapour Pressure to Relative Humidity Converter
- Specific Volume and Vapour Pressure to Enthalpy Converter
- Specific Volume and Vapour Pressure to Wet Bulb Temperature Converter
- Specific Volume and Vapour Pressure to Dew Point Temperature Converter