Use the supplied dry bulb temperature and find W from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Dew Point Temperature 14.196543 °C · height 0 m
Enthalpy = 52.90 kJ/kg dry air
More calculations with these inputs
Dry Bulb Temperature and Dew Point Temperature to All Properties
- Dry Bulb Temperature and Dew Point Temperature to Specific Humidity Converter
- Dry Bulb Temperature and Dew Point Temperature to Relative Humidity Converter
- Dry Bulb Temperature and Dew Point Temperature to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Dew Point Temperature to Specific Volume Converter
- Dry Bulb Temperature and Dew Point Temperature to Vapour Pressure Converter