← Main psychrometric calculator
Dry Bulb Temperature and Dew Point Temperature to Specific Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate specific humidity.
Calculator inputs
Specific Humidity
kg water/kg moist air
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Formula for specific humidity
Mass of water vapour divided by the total mass of moist air.
q = W / (1 + W)
Symbols
- Tdp
- Dew point temperature (DP), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Dew Point Temperature 14.196543 °C · height 0 m
Specific Humidity = 0.0100000 kg water/kg moist air
More calculations with these inputs
Dry Bulb Temperature and Dew Point Temperature to All Properties
- Dry Bulb Temperature and Dew Point Temperature to Relative Humidity Converter
- Dry Bulb Temperature and Dew Point Temperature to Enthalpy Converter
- Dry Bulb Temperature and Dew Point Temperature to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Dew Point Temperature to Specific Volume Converter
- Dry Bulb Temperature and Dew Point Temperature to Vapour Pressure Converter