Dry Bulb Temperature and Enthalpy to Relative Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate relative humidity.
Calculator inputs
Relative Humidity
%
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = (h − 1.005 Tdb) / (2500 + 1.88 Tdb)
Formula for relative humidity
Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
Worked example
Dry Bulb Temperature 27 °C · Enthalpy 52.900253 kJ/kg dry air · height 0 m
Relative Humidity = 45.39 %
More calculations with these inputs
Dry Bulb Temperature and Enthalpy to All Properties
- Dry Bulb Temperature and Enthalpy to Specific Humidity Converter
- Dry Bulb Temperature and Enthalpy to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Enthalpy to Specific Volume Converter
- Dry Bulb Temperature and Enthalpy to Vapour Pressure Converter
- Dry Bulb Temperature and Enthalpy to Dew Point Temperature Converter