Dry Bulb Temperature and Enthalpy to Specific Humidity Converter

Enter the known properties and either total pressure or height above sea level to calculate specific humidity.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Specific Humidity

— kg water/kg moist air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use the supplied dry bulb temperature and find W from the second property.

    W = (h − 1.005 Tdb) / (2500 + 1.88 Tdb)

    Formula for specific humidity

    Mass of water vapour divided by the total mass of moist air.

    q = W / (1 + W)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    q
    Specific humidity (SH), in kg water/kg moist air.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.

    Quantity definitions and calculation range

    Worked example

    Dry Bulb Temperature 27 °C · Enthalpy 52.900253 kJ/kg dry air · height 0 m

    Specific Humidity = 0.0100000 kg water/kg moist air

    More calculations with these inputs

    Dry Bulb Temperature and Enthalpy to All Properties