← Main psychrometric calculator
Dry Bulb Temperature and Relative Humidity to All Properties
Calculate the moist-air properties from dry bulb temperature and relative humidity.
Calculator inputs
Output properties
| Property | Value | Unit |
|---|---|---|
| Dry Bulb Temperature DB | °C | |
| Specific Humidity SH | kg water/kg moist air | |
| Relative Humidity RH | % | |
| Enthalpy ET | kJ/kg dry air | |
| Wet Bulb Temperature WB | °C | |
| Specific Volume SV | m³/kg dry air | |
| Vapour Pressure PV | kPa | |
| Dew Point Temperature DP | °C | |
| Total Pressure PT | kPa |
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
Pv = (RH / 100) × Psat(Tdb)
W = 0.622 × Pv / (P − Pv)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Relative Humidity 45.389339 % · height 0 m
Enthalpy = 52.90 kJ/kg dry air
Calculate an individual property
- Dry Bulb Temperature and Relative Humidity to Specific Humidity Converter
- Dry Bulb Temperature and Relative Humidity to Enthalpy Converter
- Dry Bulb Temperature and Relative Humidity to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Relative Humidity to Specific Volume Converter
- Dry Bulb Temperature and Relative Humidity to Vapour Pressure Converter
- Dry Bulb Temperature and Relative Humidity to Dew Point Temperature Converter