Dry Bulb Temperature and Relative Humidity to Specific Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate specific humidity.
Calculator inputs
Specific Humidity
kg water/kg moist air
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
Pv = (RH / 100) × Psat(Tdb)
W = 0.622 × Pv / (P − Pv)
Formula for specific humidity
Mass of water vapour divided by the total mass of moist air.
q = W / (1 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Relative Humidity 45.389339 % · height 0 m
Specific Humidity = 0.0100000 kg water/kg moist air
More calculations with these inputs
Dry Bulb Temperature and Relative Humidity to All Properties
- Dry Bulb Temperature and Relative Humidity to Enthalpy Converter
- Dry Bulb Temperature and Relative Humidity to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Relative Humidity to Specific Volume Converter
- Dry Bulb Temperature and Relative Humidity to Vapour Pressure Converter
- Dry Bulb Temperature and Relative Humidity to Dew Point Temperature Converter