← Main psychrometric calculator
Relative Humidity and Vapour Pressure to Dew Point Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate dew point temperature.
Calculator inputs
Dew Point Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = 0.622 × Pv / (P − Pv)
Psat(Tdb) = 100 Pv / RH
Formula for dew point temperature
The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.
Psat(Tdp) = Pv
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Relative Humidity 45.389339 % · Vapour Pressure 1.6191793 kPa · height 0 m
Dew Point Temperature = 14.20 °C
More calculations with these inputs
Relative Humidity and Vapour Pressure to All Properties
- Relative Humidity and Vapour Pressure to Dry Bulb Temperature Converter
- Relative Humidity and Vapour Pressure to Specific Humidity Converter
- Relative Humidity and Vapour Pressure to Enthalpy Converter
- Relative Humidity and Vapour Pressure to Wet Bulb Temperature Converter
- Relative Humidity and Vapour Pressure to Specific Volume Converter