Relative Humidity and Vapour Pressure to Specific Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate specific humidity.
Calculator inputs
Specific Humidity
kg water/kg moist air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = 0.622 × Pv / (P − Pv)
Psat(Tdb) = 100 Pv / RH
Formula for specific humidity
Mass of water vapour divided by the total mass of moist air.
q = W / (1 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Relative Humidity 45.389339 % · Vapour Pressure 1.6191793 kPa · height 0 m
Specific Humidity = 0.0100000 kg water/kg moist air
More calculations with these inputs
Relative Humidity and Vapour Pressure to All Properties
- Relative Humidity and Vapour Pressure to Dry Bulb Temperature Converter
- Relative Humidity and Vapour Pressure to Enthalpy Converter
- Relative Humidity and Vapour Pressure to Wet Bulb Temperature Converter
- Relative Humidity and Vapour Pressure to Specific Volume Converter
- Relative Humidity and Vapour Pressure to Dew Point Temperature Converter