← Main psychrometric calculator
Relative Humidity and Wet Bulb Temperature to All Properties
Calculate the moist-air properties from relative humidity and wet bulb temperature.
Calculator inputs
Output properties
| Property | Value | Unit |
|---|---|---|
| Dry Bulb Temperature DB | °C | |
| Specific Humidity SH | kg water/kg moist air | |
| Relative Humidity RH | % | |
| Enthalpy ET | kJ/kg dry air | |
| Wet Bulb Temperature WB | °C | |
| Specific Volume SV | m³/kg dry air | |
| Vapour Pressure PV | kPa | |
| Dew Point Temperature DP | °C | |
| Total Pressure PT | kPa |
Calculation history
No calculations saved on this page yet.
Input calculation
Use the wet bulb energy balance for W as a function of dry bulb temperature. Search for the temperature that matches the other known property.
W(Tdb) = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
Pv = P W / (0.622 + W)
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Relative Humidity 45.389339 % · Wet Bulb Temperature 18.724547 °C · height 0 m
Enthalpy = 52.90 kJ/kg dry air
Calculate an individual property
- Relative Humidity and Wet Bulb Temperature to Dry Bulb Temperature Converter
- Relative Humidity and Wet Bulb Temperature to Specific Humidity Converter
- Relative Humidity and Wet Bulb Temperature to Enthalpy Converter
- Relative Humidity and Wet Bulb Temperature to Specific Volume Converter
- Relative Humidity and Wet Bulb Temperature to Vapour Pressure Converter
- Relative Humidity and Wet Bulb Temperature to Dew Point Temperature Converter