Relative Humidity and Wet Bulb Temperature to Specific Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate specific humidity.
Calculator inputs
Specific Humidity
kg water/kg moist air
Calculation history
No calculations saved on this page yet.
Input calculation
Use the wet bulb energy balance for W as a function of dry bulb temperature. Search for the temperature that matches the other known property.
W(Tdb) = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
Pv = P W / (0.622 + W)
RH = 100 × Pv / Psat(Tdb)
Formula for specific humidity
Mass of water vapour divided by the total mass of moist air.
q = W / (1 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Relative Humidity 45.389339 % · Wet Bulb Temperature 18.724547 °C · height 0 m
Specific Humidity = 0.0100000 kg water/kg moist air
More calculations with these inputs
Relative Humidity and Wet Bulb Temperature to All Properties
- Relative Humidity and Wet Bulb Temperature to Dry Bulb Temperature Converter
- Relative Humidity and Wet Bulb Temperature to Enthalpy Converter
- Relative Humidity and Wet Bulb Temperature to Specific Volume Converter
- Relative Humidity and Wet Bulb Temperature to Vapour Pressure Converter
- Relative Humidity and Wet Bulb Temperature to Dew Point Temperature Converter