← Main psychrometric calculator
Specific Humidity and Relative Humidity to Dew Point Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate dew point temperature.
Calculator inputs
Dew Point Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Pv = P W / (0.622 + W)
Psat(Tdb) = 100 Pv / RH
Formula for dew point temperature
The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.
Psat(Tdp) = Pv
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Relative Humidity 45.389339 % · height 0 m
Dew Point Temperature = 14.20 °C
More calculations with these inputs
Specific Humidity and Relative Humidity to All Properties
- Specific Humidity and Relative Humidity to Dry Bulb Temperature Converter
- Specific Humidity and Relative Humidity to Enthalpy Converter
- Specific Humidity and Relative Humidity to Wet Bulb Temperature Converter
- Specific Humidity and Relative Humidity to Specific Volume Converter
- Specific Humidity and Relative Humidity to Vapour Pressure Converter