← Main psychrometric calculator
Specific Humidity and Relative Humidity to Enthalpy Converter
Enter the known properties and either total pressure or height above sea level to calculate enthalpy.
Calculator inputs
Enthalpy
kJ/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Pv = P W / (0.622 + W)
Psat(Tdb) = 100 Pv / RH
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Relative Humidity 45.389339 % · height 0 m
Enthalpy = 52.90 kJ/kg dry air
More calculations with these inputs
Specific Humidity and Relative Humidity to All Properties
- Specific Humidity and Relative Humidity to Dry Bulb Temperature Converter
- Specific Humidity and Relative Humidity to Wet Bulb Temperature Converter
- Specific Humidity and Relative Humidity to Specific Volume Converter
- Specific Humidity and Relative Humidity to Vapour Pressure Converter