Dry Bulb Temperature and Specific Humidity to Dew Point Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate dew point temperature.
Calculator inputs
Dew Point Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = q / (1 − q)
Formula for dew point temperature
The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.
Psat(Tdp) = Pv
Symbols
- Tdp
- Dew point temperature (DP), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
Worked example
Dry Bulb Temperature 27 °C · Specific Humidity 0.01 kg water/kg moist air · height 0 m
Dew Point Temperature = 14.20 °C
More calculations with these inputs
Dry Bulb Temperature and Specific Humidity to All Properties
- Dry Bulb Temperature and Specific Humidity to Relative Humidity Converter
- Dry Bulb Temperature and Specific Humidity to Enthalpy Converter
- Dry Bulb Temperature and Specific Humidity to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Specific Humidity to Specific Volume Converter
- Dry Bulb Temperature and Specific Humidity to Vapour Pressure Converter