Use the supplied dry bulb temperature and find W from the second property.
W = q / (1 − q)
Formula for specific volume
Volume occupied by the moist-air mixture per kilogram of dry air.
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- v
- Specific volume (SV), in m³/kg dry air.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Specific Humidity 0.01 kg water/kg moist air · height 0 m
Specific Volume = 0.86427 m³/kg dry air