← Main psychrometric calculator
Dry Bulb Temperature and Specific Humidity to Wet Bulb Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate wet bulb temperature.
Calculator inputs
Wet Bulb Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = q / (1 − q)
Formula for wet bulb temperature
The temperature approached when water evaporates into air adiabatically until the air reaches saturation.
h(Tdb, W) + (Ws(Twb) − W) hf(Twb) = h(Twb, Ws(Twb))
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
Worked example
Dry Bulb Temperature 27 °C · Specific Humidity 0.01 kg water/kg moist air · height 0 m
Wet Bulb Temperature = 18.72 °C
More calculations with these inputs
Dry Bulb Temperature and Specific Humidity to All Properties
- Dry Bulb Temperature and Specific Humidity to Relative Humidity Converter
- Dry Bulb Temperature and Specific Humidity to Enthalpy Converter
- Dry Bulb Temperature and Specific Humidity to Specific Volume Converter
- Dry Bulb Temperature and Specific Humidity to Vapour Pressure Converter
- Dry Bulb Temperature and Specific Humidity to Dew Point Temperature Converter