Dry Bulb Temperature and Wet Bulb Temperature to All Properties
Calculate the moist-air properties from dry bulb temperature and wet bulb temperature.
Calculator inputs
Output properties
| Property | Value | Unit |
|---|---|---|
| Dry Bulb Temperature DB | °C | |
| Specific Humidity SH | kg water/kg moist air | |
| Relative Humidity RH | % | |
| Enthalpy ET | kJ/kg dry air | |
| Wet Bulb Temperature WB | °C | |
| Specific Volume SV | m³/kg dry air | |
| Vapour Pressure PV | kPa | |
| Dew Point Temperature DP | °C | |
| Total Pressure PT | kPa |
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
Worked example
Dry Bulb Temperature 27 °C · Wet Bulb Temperature 18.724547 °C · height 0 m
Enthalpy = 52.90 kJ/kg dry air
Calculate an individual property
- Dry Bulb Temperature and Wet Bulb Temperature to Specific Humidity Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Relative Humidity Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Enthalpy Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Specific Volume Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Vapour Pressure Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Dew Point Temperature Converter