← Main psychrometric calculator
Dry Bulb Temperature and Wet Bulb Temperature to Vapour Pressure Converter
Enter the known properties and either total pressure or height above sea level to calculate vapour pressure.
Calculator inputs
Vapour Pressure
kPa
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
Formula for vapour pressure
The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.
Pv = P W / (0.622 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Wet Bulb Temperature 18.724547 °C · height 0 m
Vapour Pressure = 1.61918 kPa
More calculations with these inputs
Dry Bulb Temperature and Wet Bulb Temperature to All Properties
- Dry Bulb Temperature and Wet Bulb Temperature to Specific Humidity Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Relative Humidity Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Enthalpy Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Specific Volume Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Dew Point Temperature Converter