    Use the supplied dry bulb temperature and find W from the second property.

    W = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]

    Formula for vapour pressure

    The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.

    Pv = P W / (0.622 + W)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    Pv
    Water vapour partial pressure (PV), in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Dry Bulb Temperature 27 °C · Wet Bulb Temperature 18.724547 °C · height 0 m

    Vapour Pressure = 1.61918 kPa