← Main psychrometric calculator
Dry Bulb Temperature and Wet Bulb Temperature to Enthalpy Converter
Enter the known properties and either total pressure or height above sea level to calculate enthalpy.
Calculator inputs
Enthalpy
kJ/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
Worked example
Dry Bulb Temperature 27 °C · Wet Bulb Temperature 18.724547 °C · height 0 m
Enthalpy = 52.90 kJ/kg dry air
More calculations with these inputs
Dry Bulb Temperature and Wet Bulb Temperature to All Properties
- Dry Bulb Temperature and Wet Bulb Temperature to Specific Humidity Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Relative Humidity Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Specific Volume Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Vapour Pressure Converter
- Dry Bulb Temperature and Wet Bulb Temperature to Dew Point Temperature Converter