← Main psychrometric calculator
Enthalpy and Dew Point Temperature to Specific Volume Converter
Enter the known properties and either total pressure or height above sea level to calculate specific volume.
Calculator inputs
Specific Volume
m³/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
Formula for specific volume
Volume occupied by the moist-air mixture per kilogram of dry air.
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Dew Point Temperature 14.196543 °C · height 0 m
Specific Volume = 0.86427 m³/kg dry air
More calculations with these inputs
Enthalpy and Dew Point Temperature to All Properties
- Enthalpy and Dew Point Temperature to Dry Bulb Temperature Converter
- Enthalpy and Dew Point Temperature to Specific Humidity Converter
- Enthalpy and Dew Point Temperature to Relative Humidity Converter
- Enthalpy and Dew Point Temperature to Wet Bulb Temperature Converter
- Enthalpy and Dew Point Temperature to Vapour Pressure Converter