← Main psychrometric calculator
Enthalpy and Dew Point Temperature to Wet Bulb Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate wet bulb temperature.
Calculator inputs
Wet Bulb Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
Formula for wet bulb temperature
The temperature approached when water evaporates into air adiabatically until the air reaches saturation.
h(Tdb, W) + (Ws(Twb) − W) hf(Twb) = h(Twb, Ws(Twb))
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Dew Point Temperature 14.196543 °C · height 0 m
Wet Bulb Temperature = 18.72 °C
More calculations with these inputs
Enthalpy and Dew Point Temperature to All Properties
- Enthalpy and Dew Point Temperature to Dry Bulb Temperature Converter
- Enthalpy and Dew Point Temperature to Specific Humidity Converter
- Enthalpy and Dew Point Temperature to Relative Humidity Converter
- Enthalpy and Dew Point Temperature to Specific Volume Converter
- Enthalpy and Dew Point Temperature to Vapour Pressure Converter