← Main psychrometric calculator
Enthalpy and Dew Point Temperature to Vapour Pressure Converter
Enter the known properties and either total pressure or height above sea level to calculate vapour pressure.
Calculator inputs
Vapour Pressure
kPa
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
Formula for vapour pressure
The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.
Pv = P W / (0.622 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Dew Point Temperature 14.196543 °C · height 0 m
Vapour Pressure = 1.61918 kPa
More calculations with these inputs
Enthalpy and Dew Point Temperature to All Properties
- Enthalpy and Dew Point Temperature to Dry Bulb Temperature Converter
- Enthalpy and Dew Point Temperature to Specific Humidity Converter
- Enthalpy and Dew Point Temperature to Relative Humidity Converter
- Enthalpy and Dew Point Temperature to Wet Bulb Temperature Converter
- Enthalpy and Dew Point Temperature to Specific Volume Converter