← Main psychrometric calculator
Specific Humidity and Enthalpy to Dew Point Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate dew point temperature.
Calculator inputs
Dew Point Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
Formula for dew point temperature
The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.
Psat(Tdp) = Pv
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Enthalpy 52.900253 kJ/kg dry air · height 0 m
Dew Point Temperature = 14.20 °C
More calculations with these inputs
Specific Humidity and Enthalpy to All Properties
- Specific Humidity and Enthalpy to Dry Bulb Temperature Converter
- Specific Humidity and Enthalpy to Relative Humidity Converter
- Specific Humidity and Enthalpy to Wet Bulb Temperature Converter
- Specific Humidity and Enthalpy to Specific Volume Converter
- Specific Humidity and Enthalpy to Vapour Pressure Converter