← Main psychrometric calculator
Specific Humidity and Enthalpy to Wet Bulb Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate wet bulb temperature.
Calculator inputs
Wet Bulb Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
Formula for wet bulb temperature
The temperature approached when water evaporates into air adiabatically until the air reaches saturation.
h(Tdb, W) + (Ws(Twb) − W) hf(Twb) = h(Twb, Ws(Twb))
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Enthalpy 52.900253 kJ/kg dry air · height 0 m
Wet Bulb Temperature = 18.72 °C
More calculations with these inputs
Specific Humidity and Enthalpy to All Properties
- Specific Humidity and Enthalpy to Dry Bulb Temperature Converter
- Specific Humidity and Enthalpy to Relative Humidity Converter
- Specific Humidity and Enthalpy to Specific Volume Converter
- Specific Humidity and Enthalpy to Vapour Pressure Converter
- Specific Humidity and Enthalpy to Dew Point Temperature Converter