← Main psychrometric calculator
Specific Humidity and Enthalpy to Vapour Pressure Converter
Enter the known properties and either total pressure or height above sea level to calculate vapour pressure.
Calculator inputs
Vapour Pressure
kPa
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Tdb = (h − 2500 W) / (1.005 + 1.88 W)
Formula for vapour pressure
The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.
Pv = P W / (0.622 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Enthalpy 52.900253 kJ/kg dry air · height 0 m
Vapour Pressure = 1.61918 kPa
More calculations with these inputs
Specific Humidity and Enthalpy to All Properties
- Specific Humidity and Enthalpy to Dry Bulb Temperature Converter
- Specific Humidity and Enthalpy to Relative Humidity Converter
- Specific Humidity and Enthalpy to Wet Bulb Temperature Converter
- Specific Humidity and Enthalpy to Specific Volume Converter
- Specific Humidity and Enthalpy to Dew Point Temperature Converter