    Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.

    W = q / (1 − q)
    Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)

    Formula for dew point temperature

    The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.

    Psat(Tdp) = Pv

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    Tdp
    Dew point temperature (DP), in °C.
    q
    Specific humidity (SH), in kg water/kg moist air.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    Pv
    Water vapour partial pressure (PV), in kPa.
    Psat
    Saturation vapour pressure at the temperature in parentheses, in kPa.

    Quantity definitions and calculation range

    Worked example

    Specific Humidity 0.01 kg water/kg moist air · Wet Bulb Temperature 18.724547 °C · height 0 m

    Dew Point Temperature = 14.20 °C