← Main psychrometric calculator
Specific Humidity and Wet Bulb Temperature to Dew Point Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate dew point temperature.
Calculator inputs
Dew Point Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)
Formula for dew point temperature
The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.
Psat(Tdp) = Pv
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Wet Bulb Temperature 18.724547 °C · height 0 m
Dew Point Temperature = 14.20 °C
More calculations with these inputs
Specific Humidity and Wet Bulb Temperature to All Properties
- Specific Humidity and Wet Bulb Temperature to Dry Bulb Temperature Converter
- Specific Humidity and Wet Bulb Temperature to Relative Humidity Converter
- Specific Humidity and Wet Bulb Temperature to Enthalpy Converter
- Specific Humidity and Wet Bulb Temperature to Specific Volume Converter
- Specific Humidity and Wet Bulb Temperature to Vapour Pressure Converter