← Main psychrometric calculator
Specific Humidity and Wet Bulb Temperature to Relative Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate relative humidity.
Calculator inputs
Relative Humidity
%
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
W = q / (1 − q)
Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)
Formula for relative humidity
Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- q
- Specific humidity (SH), in kg water/kg moist air.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- RH
- Relative humidity, in percent.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
Worked example
Specific Humidity 0.01 kg water/kg moist air · Wet Bulb Temperature 18.724547 °C · height 0 m
Relative Humidity = 45.39 %
More calculations with these inputs
Specific Humidity and Wet Bulb Temperature to All Properties
- Specific Humidity and Wet Bulb Temperature to Dry Bulb Temperature Converter
- Specific Humidity and Wet Bulb Temperature to Enthalpy Converter
- Specific Humidity and Wet Bulb Temperature to Specific Volume Converter
- Specific Humidity and Wet Bulb Temperature to Vapour Pressure Converter
- Specific Humidity and Wet Bulb Temperature to Dew Point Temperature Converter