← Main psychrometric calculator

Specific Humidity and Wet Bulb Temperature to Specific Volume Converter

Enter the known properties and either total pressure or height above sea level to calculate specific volume.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Specific Volume

— m³/kg dry air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.

    W = q / (1 − q)
    Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)

    Formula for specific volume

    Volume occupied by the moist-air mixture per kilogram of dry air.

    v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    q
    Specific humidity (SH), in kg water/kg moist air.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    v
    Specific volume (SV), in m³/kg dry air.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Specific Humidity 0.01 kg water/kg moist air · Wet Bulb Temperature 18.724547 °C · height 0 m

    Specific Volume = 0.86427 m³/kg dry air

    More calculations with these inputs