← Main psychrometric calculator
Wet Bulb Temperature and Dew Point Temperature to All Properties
Calculate the moist-air properties from wet bulb temperature and dew point temperature.
Calculator inputs
Output properties
| Property | Value | Unit |
|---|---|---|
| Dry Bulb Temperature DB | °C | |
| Specific Humidity SH | kg water/kg moist air | |
| Relative Humidity RH | % | |
| Enthalpy ET | kJ/kg dry air | |
| Wet Bulb Temperature WB | °C | |
| Specific Volume SV | m³/kg dry air | |
| Vapour Pressure PV | kPa | |
| Dew Point Temperature DP | °C | |
| Total Pressure PT | kPa |
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Wet Bulb Temperature 18.724547 °C · Dew Point Temperature 14.196543 °C · height 0 m
Enthalpy = 52.90 kJ/kg dry air
Calculate an individual property
- Wet Bulb Temperature and Dew Point Temperature to Dry Bulb Temperature Converter
- Wet Bulb Temperature and Dew Point Temperature to Specific Humidity Converter
- Wet Bulb Temperature and Dew Point Temperature to Relative Humidity Converter
- Wet Bulb Temperature and Dew Point Temperature to Enthalpy Converter
- Wet Bulb Temperature and Dew Point Temperature to Specific Volume Converter
- Wet Bulb Temperature and Dew Point Temperature to Vapour Pressure Converter