← Main psychrometric calculator
Wet Bulb Temperature and Dew Point Temperature to Specific Volume Converter
Enter the known properties and either total pressure or height above sea level to calculate specific volume.
Calculator inputs
Specific Volume
m³/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Obtain the moisture term from the first reading, then calculate the dry bulb temperature from the second property.
Pv = Psat(Tdp)
W = 0.622 × Pv / (P − Pv)
Tdb = [h(Twb, Ws) − (Ws − W) hf(Twb) − 2500 W] / (1.005 + 1.88 W)
Formula for specific volume
Volume occupied by the moist-air mixture per kilogram of dry air.
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- Tdp
- Dew point temperature (DP), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Wet Bulb Temperature 18.724547 °C · Dew Point Temperature 14.196543 °C · height 0 m
Specific Volume = 0.86427 m³/kg dry air
More calculations with these inputs
Wet Bulb Temperature and Dew Point Temperature to All Properties
- Wet Bulb Temperature and Dew Point Temperature to Dry Bulb Temperature Converter
- Wet Bulb Temperature and Dew Point Temperature to Specific Humidity Converter
- Wet Bulb Temperature and Dew Point Temperature to Relative Humidity Converter
- Wet Bulb Temperature and Dew Point Temperature to Enthalpy Converter
- Wet Bulb Temperature and Dew Point Temperature to Vapour Pressure Converter