← Main psychrometric calculator

Wet Bulb Temperature and Specific Volume to Dry Bulb Temperature Converter

Enter the known properties and either total pressure or height above sea level to calculate dry bulb temperature.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Dry Bulb Temperature

— °C

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use the wet bulb energy balance for W as a function of dry bulb temperature. Search for the temperature that matches the other known property.

    W(Tdb) = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
    v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P

    Reading dry bulb temperature

    Air temperature measured by a dry, shielded thermometer.

    The input calculation above gives the dry bulb temperature directly or by solving for it.

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    v
    Specific volume (SV), in m³/kg dry air.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Wet Bulb Temperature 18.724547 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m

    Dry Bulb Temperature = 27.00 °C

    More calculations with these inputs

    Wet Bulb Temperature and Specific Volume to All Properties