Wet Bulb Temperature and Specific Volume to Enthalpy Converter
Enter the known properties and either total pressure or height above sea level to calculate enthalpy.
Calculator inputs
Enthalpy
kJ/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Use the wet bulb energy balance for W as a function of dry bulb temperature. Search for the temperature that matches the other known property.
W(Tdb) = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- v
- Specific volume (SV), in m³/kg dry air.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Wet Bulb Temperature 18.724547 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Enthalpy = 52.90 kJ/kg dry air
More calculations with these inputs
Wet Bulb Temperature and Specific Volume to All Properties
- Wet Bulb Temperature and Specific Volume to Dry Bulb Temperature Converter
- Wet Bulb Temperature and Specific Volume to Specific Humidity Converter
- Wet Bulb Temperature and Specific Volume to Relative Humidity Converter
- Wet Bulb Temperature and Specific Volume to Vapour Pressure Converter
- Wet Bulb Temperature and Specific Volume to Dew Point Temperature Converter