← Main psychrometric calculator

Wet Bulb Temperature and Specific Volume to Vapour Pressure Converter

Enter the known properties and either total pressure or height above sea level to calculate vapour pressure.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Vapour Pressure

— kPa

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use the wet bulb energy balance for W as a function of dry bulb temperature. Search for the temperature that matches the other known property.

    W(Tdb) = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
    v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P

    Formula for vapour pressure

    The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.

    Pv = P W / (0.622 + W)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Twb
    Wet bulb temperature (WB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Ws
    Saturated value of W at the indicated temperature.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    hf
    Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
    v
    Specific volume (SV), in m³/kg dry air.
    Pv
    Water vapour partial pressure (PV), in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Wet Bulb Temperature 18.724547 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m

    Vapour Pressure = 1.61918 kPa

    More calculations with these inputs

    Wet Bulb Temperature and Specific Volume to All Properties