← Main psychrometric calculator
Wet Bulb Temperature and Specific Volume to Vapour Pressure Converter
Enter the known properties and either total pressure or height above sea level to calculate vapour pressure.
Calculator inputs
Vapour Pressure
kPa
Calculation history
No calculations saved on this page yet.
Input calculation
Use the wet bulb energy balance for W as a function of dry bulb temperature. Search for the temperature that matches the other known property.
W(Tdb) = [h(Twb, Ws) − Ws hf(Twb) − 1.005 Tdb] / [2500 + 1.88 Tdb − hf(Twb)]
v = 0.2871 (Tdb + 273.15)(1 + W/0.622) / P
Formula for vapour pressure
The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.
Pv = P W / (0.622 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Wet Bulb Temperature 18.724547 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Vapour Pressure = 1.61918 kPa
More calculations with these inputs
Wet Bulb Temperature and Specific Volume to All Properties
- Wet Bulb Temperature and Specific Volume to Dry Bulb Temperature Converter
- Wet Bulb Temperature and Specific Volume to Specific Humidity Converter
- Wet Bulb Temperature and Specific Volume to Relative Humidity Converter
- Wet Bulb Temperature and Specific Volume to Enthalpy Converter
- Wet Bulb Temperature and Specific Volume to Dew Point Temperature Converter