Dry Bulb Temperature and Specific Volume to Dew Point Temperature Converter

Enter the known properties and either total pressure or height above sea level to calculate dew point temperature.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Dew Point Temperature

— °C

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use the supplied dry bulb temperature and find W from the second property.

    W = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]

    Formula for dew point temperature

    The temperature at which air becomes saturated when cooled at the same water vapour partial pressure. Below freezing the calculation uses saturation over ice.

    Psat(Tdp) = Pv

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    Tdp
    Dew point temperature (DP), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    v
    Specific volume (SV), in m³/kg dry air.
    Pv
    Water vapour partial pressure (PV), in kPa.
    Psat
    Saturation vapour pressure at the temperature in parentheses, in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Dry Bulb Temperature 27 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m

    Dew Point Temperature = 14.20 °C