Use the supplied dry bulb temperature and find W from the second property.
W = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- v
- Specific volume (SV), in m³/kg dry air.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Enthalpy = 52.90 kJ/kg dry air