← Main psychrometric calculator
Dry Bulb Temperature and Specific Volume to Vapour Pressure Converter
Enter the known properties and either total pressure or height above sea level to calculate vapour pressure.
Calculator inputs
Vapour Pressure
kPa
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
Formula for vapour pressure
The portion of the total air pressure contributed by water vapour. Also spelled vapor pressure.
Pv = P W / (0.622 + W)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Vapour Pressure = 1.61918 kPa
More calculations with these inputs
Dry Bulb Temperature and Specific Volume to All Properties
- Dry Bulb Temperature and Specific Volume to Specific Humidity Converter
- Dry Bulb Temperature and Specific Volume to Relative Humidity Converter
- Dry Bulb Temperature and Specific Volume to Enthalpy Converter
- Dry Bulb Temperature and Specific Volume to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Specific Volume to Dew Point Temperature Converter