Dry Bulb Temperature and Specific Volume to Relative Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate relative humidity.
Calculator inputs
Relative Humidity
%
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
Formula for relative humidity
Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- v
- Specific volume (SV), in m³/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Relative Humidity = 45.39 %