← Main psychrometric calculator
Dry Bulb Temperature and Vapour Pressure to Enthalpy Converter
Enter the known properties and either total pressure or height above sea level to calculate enthalpy.
Calculator inputs
Enthalpy
kJ/kg dry air
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = 0.622 × Pv / (P − Pv)
Formula for enthalpy
Sensible and latent energy of moist air per kilogram of dry air, relative to the model’s reference state.
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Vapour Pressure 1.6191793 kPa · height 0 m
Enthalpy = 52.90 kJ/kg dry air
More calculations with these inputs
Dry Bulb Temperature and Vapour Pressure to All Properties
- Dry Bulb Temperature and Vapour Pressure to Specific Humidity Converter
- Dry Bulb Temperature and Vapour Pressure to Relative Humidity Converter
- Dry Bulb Temperature and Vapour Pressure to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Vapour Pressure to Specific Volume Converter
- Dry Bulb Temperature and Vapour Pressure to Dew Point Temperature Converter