Dry Bulb Temperature and Vapour Pressure to Wet Bulb Temperature Converter
Enter the known properties and either total pressure or height above sea level to calculate wet bulb temperature.
Calculator inputs
Wet Bulb Temperature
°C
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = 0.622 × Pv / (P − Pv)
Formula for wet bulb temperature
The temperature approached when water evaporates into air adiabatically until the air reaches saturation.
h(Tdb, W) + (Ws(Twb) − W) hf(Twb) = h(Twb, Ws(Twb))
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- Twb
- Wet bulb temperature (WB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- Ws
- Saturated value of W at the indicated temperature.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- hf
- Enthalpy of liquid water or ice at the wet bulb temperature relative to liquid water at 0 °C, in kJ/kg water.
- Pv
- Water vapour partial pressure (PV), in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Vapour Pressure 1.6191793 kPa · height 0 m
Wet Bulb Temperature = 18.72 °C
More calculations with these inputs
Dry Bulb Temperature and Vapour Pressure to All Properties
- Dry Bulb Temperature and Vapour Pressure to Specific Humidity Converter
- Dry Bulb Temperature and Vapour Pressure to Relative Humidity Converter
- Dry Bulb Temperature and Vapour Pressure to Enthalpy Converter
- Dry Bulb Temperature and Vapour Pressure to Specific Volume Converter
- Dry Bulb Temperature and Vapour Pressure to Dew Point Temperature Converter