Dry Bulb Temperature and Vapour Pressure to Relative Humidity Converter
Enter the known properties and either total pressure or height above sea level to calculate relative humidity.
Calculator inputs
Relative Humidity
%
Calculation history
No calculations saved on this page yet.
Input calculation
Use the supplied dry bulb temperature and find W from the second property.
W = 0.622 × Pv / (P − Pv)
Formula for relative humidity
Water vapour partial pressure expressed as a percentage of saturation pressure at the dry bulb temperature.
RH = 100 × Pv / Psat(Tdb)
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- RH
- Relative humidity, in percent.
- Pv
- Water vapour partial pressure (PV), in kPa.
- Psat
- Saturation vapour pressure at the temperature in parentheses, in kPa.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Dry Bulb Temperature 27 °C · Vapour Pressure 1.6191793 kPa · height 0 m
Relative Humidity = 45.39 %
More calculations with these inputs
Dry Bulb Temperature and Vapour Pressure to All Properties
- Dry Bulb Temperature and Vapour Pressure to Specific Humidity Converter
- Dry Bulb Temperature and Vapour Pressure to Enthalpy Converter
- Dry Bulb Temperature and Vapour Pressure to Wet Bulb Temperature Converter
- Dry Bulb Temperature and Vapour Pressure to Specific Volume Converter
- Dry Bulb Temperature and Vapour Pressure to Dew Point Temperature Converter