← Main psychrometric calculator

Dry Bulb Temperature and Vapour Pressure to Specific Humidity Converter

Enter the known properties and either total pressure or height above sea level to calculate specific humidity.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Specific Humidity

— kg water/kg moist air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use the supplied dry bulb temperature and find W from the second property.

    W = 0.622 × Pv / (P − Pv)

    Formula for specific humidity

    Mass of water vapour divided by the total mass of moist air.

    q = W / (1 + W)

    Symbols

    q
    Specific humidity (SH), in kg water/kg moist air.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    Pv
    Water vapour partial pressure (PV), in kPa.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Dry Bulb Temperature 27 °C · Vapour Pressure 1.6191793 kPa · height 0 m

    Specific Humidity = 0.0100000 kg water/kg moist air

    More calculations with these inputs

    Dry Bulb Temperature and Vapour Pressure to All Properties