Input calculation
Use specific volume to express W as a function of dry bulb temperature. Solve the enthalpy equation for that temperature.
W(Tdb) = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
h = 1.005 Tdb + W (2500 + 1.88 Tdb)
Reading dry bulb temperature
Air temperature measured by a dry, shielded thermometer.
The input calculation above gives the dry bulb temperature directly or by solving for it.
Symbols
- Tdb
- Dry bulb temperature (DB), in °C.
- W
- Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
- h
- Moist-air enthalpy (ET), in kJ/kg dry air.
- v
- Specific volume (SV), in m³/kg dry air.
- P
- Total atmospheric pressure (PT), in kPa.
Worked example
Enthalpy 52.900253 kJ/kg dry air · Specific Volume 0.86427316 m³/kg dry air · height 0 m
Dry Bulb Temperature = 27.00 °C
More calculations with these inputs
Enthalpy and Specific Volume to All Properties
- Enthalpy and Specific Volume to Specific Humidity Converter
- Enthalpy and Specific Volume to Relative Humidity Converter
- Enthalpy and Specific Volume to Wet Bulb Temperature Converter
- Enthalpy and Specific Volume to Vapour Pressure Converter
- Enthalpy and Specific Volume to Dew Point Temperature Converter