← Main psychrometric calculator

Enthalpy and Specific Volume to Dry Bulb Temperature Converter

Enter the known properties and either total pressure or height above sea level to calculate dry bulb temperature.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Dry Bulb Temperature

— °C

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use specific volume to express W as a function of dry bulb temperature. Solve the enthalpy equation for that temperature.

    W(Tdb) = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
    h = 1.005 Tdb + W (2500 + 1.88 Tdb)

    Reading dry bulb temperature

    Air temperature measured by a dry, shielded thermometer.

    The input calculation above gives the dry bulb temperature directly or by solving for it.

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    v
    Specific volume (SV), in m³/kg dry air.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Enthalpy 52.900253 kJ/kg dry air · Specific Volume 0.86427316 m³/kg dry air · height 0 m

    Dry Bulb Temperature = 27.00 °C

    More calculations with these inputs

    Enthalpy and Specific Volume to All Properties