← Main psychrometric calculator

Enthalpy and Specific Volume to Specific Humidity Converter

Enter the known properties and either total pressure or height above sea level to calculate specific humidity.

Calculator inputs

Air pressure input

Extract the full archive before opening the calculator so its scripts can load.

Specific Humidity

— kg water/kg moist air

Calculation history

No calculations saved on this page yet.

    Input calculation

    Use specific volume to express W as a function of dry bulb temperature. Solve the enthalpy equation for that temperature.

    W(Tdb) = 0.622 [P × v / (0.2871 (Tdb + 273.15)) − 1]
    h = 1.005 Tdb + W (2500 + 1.88 Tdb)

    Formula for specific humidity

    Mass of water vapour divided by the total mass of moist air.

    q = W / (1 + W)

    Symbols

    Tdb
    Dry bulb temperature (DB), in °C.
    q
    Specific humidity (SH), in kg water/kg moist air.
    W
    Intermediate water-vapour mass per kilogram of dry air, obtained from q/(1 − q) when known.
    h
    Moist-air enthalpy (ET), in kJ/kg dry air.
    v
    Specific volume (SV), in m³/kg dry air.
    P
    Total atmospheric pressure (PT), in kPa.

    Quantity definitions and calculation range

    Worked example

    Enthalpy 52.900253 kJ/kg dry air · Specific Volume 0.86427316 m³/kg dry air · height 0 m

    Specific Humidity = 0.0100000 kg water/kg moist air

    More calculations with these inputs

    Enthalpy and Specific Volume to All Properties